General information
Hardware product version 01
Firmware version V2.6
Engineering with
Programming package STEP 7 V5.4 SP2
Supply voltage
Rated value (DC) 24 V
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
External protection for supply cables (recommendation) 2 A min.
Input current
Current consumption (rated value) 650 mA
Current consumption (in no-load operation), typ. 100 mA
Rated value at 24 V DC 100 mA; idling
Inrush current, max. 2.5 A; Typical
Inrush current, typ. 2.5 A
Starting current inrush I²t 1 A²·s
I²t 1 A²·s
Power losses
Power loss, typ. 3.5 W
Memory
Type of memory other
Work memory
integrated 256 kbyte; For program and data
expandable No
Load memory
pluggable (MMC) Yes
pluggable (MMC), max. 8 Mbyte
Data management on MMC (after last programming), min. 10 a
Backup
present Yes; Guaranteed by MMC (maintenance-free)
without battery Yes; Program and data
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max. 1023; Number band: 1 to 1023
Size, max. 16 kbyte
FB
Number, max. 1024; Number range: 0 to 2047
Size, max. 16 kbyte
FC
Number, max. 1024; Number range: 0 to 2047
Size, max. 16 kbyte
OB
Size, max. 16 kbyte
Number of free cycle OBs 1; OB 1
Number of time alarm OBs 1; OB 10
Number of delay alarm OBs 1; OB 20
Number of time interrupt OBs 1; OB 35
Number of process alarm OBs 1; OB 40
Number of DPV1 alarm OBs 3; OB 55, 56, 57
Number isochronous mode OBs 1; OB 61
Number of startup OBs 1; OB 100
Number of asynchronous error OBs 6; OB 80, 82, 83, 85, 86, 87
Number of synchronous error OBs 2; OB 121, 122
Nesting depth
per priority class 8
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 256
Retentivity
adjustable Yes
lower limit 0
upper limit 255
preset 8
Counting range
adjustable Yes
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
S7 times
Number 256
Retentivity
adjustable Yes
lower limit 0
upper limit 255
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, 128 KB max.
Flag
Number, max. 2048 byte
Retentivity available Yes; MB 0 to MB 2047
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Data blocks
Number, max. 1023; Number band: 1 to 1023
Size, max. 16 kbyte
Retentivity adjustable Yes; via non-retain property on DB
Retentivity preset Yes
Local data
per priority class, max. 1024 byte; per block max. 510
Address area
I/O address area
Inputs 2 kbyte
Outputs 2 kbyte
of which, distributed
Inputs 2 kbyte
Outputs 2 kbyte
Process image
Inputs 2048 byte
Outputs 2048 byte
Inputs, adjustable 2 kbyte
Outputs, adjustable 2 kbyte
Inputs, default 128 byte
Outputs, default 128 byte
Subprocess images
Number of subprocess images, max. 1
Digital channels
Inputs 16384
Outputs 16384
Inputs, of which central 1024
Outputs, of which central 1024
Analog channels
Inputs 1024
Outputs 1024
Inputs, of which central 256
Outputs, of which central 256
Hardware configuration
Expansion devices, max. 3
Number of DP masters
integrated 1
via CP 4
Number of operable FMs and CPs (recommended)
FM 8
CP, point-to-point 8
CP, LAN 10
Rack
Racks, max. 4
Number of units / per module subrack / maximum 8
Time of day
Clock
Hardware clock (real-time clock) Yes
battery-backed and synchronizable Yes
Deviation per day, max. 10 s
Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
Number 1
Number/Number range 0
Range of values 0 to 2^31 hours (when using SFC 101)
Granularity 1 hour
retentive Yes; Must be restarted at each restart
Clock synchronization
supported Yes
to MPI, master Yes
to MPI, slave Yes
to DP, master Yes; With DP slave only slave clock
to DP, slave Yes
in AS, master Yes
in AS, slave Yes
on Ethernet via NTP Yes; as client
Digital inputs
integrated channels (DI) 0
Digital outputs
integrated channels (DO) 0
Analog inputs
Integrated channels (AI) 0
Analog outputs
Integrated channels (AO) 0
Interfaces
Number of parallel interfaces 0
Number of 20 mA interfaces (TTY) 0
Number of RS 232 interfaces 0
Number of RS 422 interfaces 0
Number of other interfaces 0
1st interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
MPI Yes
DP master Yes